Outdoor Prefabricated Combined Compact Substation
3000KVA 24.94-12.47KV
3000KVA 24.94-12.47KV
Base kVA: 45 kVA to 12,000 kVA Primary voltage: 2400 V to 46,000 V Secondary voltage: 120 V to 24,940V Basic lmpulse Level (BIL): 30kV to 250kV
| Product model | Capacity (KVA) |
Join group label | Voltage combination | No-load loss (W) |
Load loss (W) |
No-load current (%) |
Short-circuit impedance (%) |
External dimension(mm) Length × Width × Height |
|
| High tension (KV) |
Low pressure (KV) |
||||||||
| ZGS13-H-100/10 | 100 | YynO or Dyn11 |
6 6.3±5% 10±2.5% 10.5 11 |
0.4 | 150 | 1500 | 0.65 | 4.0 | 1830×1355×1735 |
| ZGS13-H-125/10 | 125 | 170 | 1800 | 0.65 | 1830×1365×1735 | ||||
| ZGS13-H-160/10 | 160 | 200 | 2200 | 0.60 | 1830×1375×1735 | ||||
| ZGS13-H-200/10 | 200 | 240 | 2600 | 0.50 | 1830×1375×1735 | ||||
| ZGS13-H-250/10 | 250 | 290 | 3050 | 0.50 | 1830×1405×1735 | ||||
| ZGS13-H-315/10 | 315 | 340 | 3650 | 0.45 | 1830×1425×1735 | ||||
| ZGS13-H-400/10 | 400 | 410 | 4300 | 0.45 | 1830×1435×1805 | ||||
| ZGS13-H-500/10 | 500 | 480 | 5150 | 0.40 | 1830×1445×1805 | ||||
| ZGS13-H-630/10 | 630 | 570 | 6200 | 0.40 | 4.5 | 1830×1455×1860 | |||
| ZGS13-H-800/10 | 800 | 700 | 7500 | 0.35 | 1830×1490×1860 | ||||
| ZGS13-H-1000/10 | 1000 | 830 | 10300 | 0.35 | 1830×1675×2005 | ||||
| ZGS13-H-1250/10 | 1250 | 970 | 12000 | 0.30 | 2100×1845×2035 | ||||
| ZGS13-H-1600/10 | 1600 | 1170 | 14500 | 0.30 | 2100×1885×2135 | ||||
Understanding Cast Resin Three-Phase Dry-Type Transformers A cast resin three-phase dry-type transformer is designed to ...
READ MOREThe pad mounted transformer is an integral part of electrical distribution systems, providing voltage transformation fro...
READ MOREIntroduction to Power Transformers and Distribution Transformers In the field of electrical engineering, transformers p...
READ MOREUnderstanding switch electrical ratings Every electrical switch is specified by voltage and current ratings (for example...
READ MORE